TK4L-14RN

Rp 980.000

(*harga termasuk pajak 10%)

2^

Data sheet

Display method 4-digit 7-segment LED
Control method ON/OFF control, P, PI, PD, PID control
Input specification Thermocouple: K(CA), J(IC), E(CR), T(CC), B(PR), R(PR), S(PR), N(NN), C(TT), G(TT), L(IC), U(CC), Platinel II
RTD: DPt100Ω, DPt50Ω, JPt100Ω, Cu100Ω, Cu50Ω, Nikel 120Ω
Analog: 0-100mV, 0-5V, 1-5V, 0-10V
0-20mA, 4-20mA
Sampling cycle 50ms
Control output 1 Relay(250VAC~ 3A)
Option input CT, Digital(DI-1)
Option output Alarm 1
Power supply 100-240VAC~ 50/60Hz
Protection structure IP65(front panel)
Display accuracy_RTD •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Thermocouple •At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
•Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit
Display accuracy_Analog •At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit
•Out of range of room temperature: ±0.5℃% F.S. ±1-digit
Display accuracy_CT input ±5% F.S. ±1-digit
Hysteresis(adjustable sensitivity) RTD/Thermocouples: 1 to 100℃/℉(0.1 to 100.0℃/℉) variable Analog: 1 to 100-digit
Proportional band 0.1 to 999.9℃/℉(0.1 to 999.9%)
Integral time 0 to 9999 sec
Derivative time 0 to 9999 sec
Control period Relay output, SSR drive output: 0.1 to 120.0 sec Current output or SSR drive output selectable: 1.0 to 120.0 sec
Manual reset 0.0 to 100.0%
Environment_Ambient temperature -10 to 50℃, storage: -20 to 60℃
Environment_Ambient humidity 35 to 85% RH, storage: 35 to 85% RH

※“S” represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are available. “C” represents selectable current and SSR drive output support models.
※Select "R" or "C" type in case of using heating&cooling control and "N" type in case of using standard control.
※CT input of TK4N is available only for the standard model which has alarm output 1.
※Display accuracy:
◎At room temperature (23℃±5℃)
• Thermocouple K, J, T, N, E type, below -100℃/Thermocouple L, U, PLⅡ type, RTD Cu50Ω, DPt50Ω: (PV ±0.3% or ±2℃, select the higher one) ±1-digit
• Thermocouple C, G, R, S type, below 200℃: (PV ±0.3% or ±3℃, select the higher one) ±1-digit
• Thermocouple B type, below 400℃: there is no accuracy standards.
◎Out of room temperature range
• RTD Cu50Ω, DPt50Ω: (PV ±0.5% or ±3℃, select the higher one) ±1-digit
• Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5℃, select the higher one) ±1-digit
• Others, Below -100℃: within ±5℃
In case of TK4SP Series, ±1℃ will be added to the degree standard.
※The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

    

TEMPERATURE CONTROLLER TD